VertX

VertX® V200 Input Monitor Interface
How To Purchase
If you would like to order our products download our easy to use How To Order Guide.
Download

VertX® V200 Input Monitor Interface
Alarm Input Processing for up to 16 Zones
Overview Key Features Specifications

The HID VertX products provide a complete and fully featured hardware/firmware infrastructure for access control software host systems. The V200 input monitor interface connects up to 16 supervised input circuits. Each input point monitors and reports normal, off-normal, and alarm states. The V200 features on-board flash memory, allowing program updates to be downloaded through the network. The V200 connects to the V1000 via a high speed RS-485 network. The V1000, in turn, communicates with the system host via industry standard TCP/IP protocol, over 10/100 Mbps Ethernet, or the Internet. This architecture minimizes the impact on corporate LANs, by using only one TCP/IP address for every 32 interfaces, and by handling low-level transactions on the RS-485 network.

  • Reports supervised or un-supervised alarm circuits.
  • Off-normal condition programmable for each input point (NO or NC alarm devices may be used).
  • Connects to the V1000 via RS-485.
  • Receives and processes real time commands from the V1000.
  • Reports all activity to the V1000.
  • Allows complex input/output linking when used with the V1000 and V300 Output Control Interface.
  • Attractive polycarbonate enclosure protects components from damage.
  • All connections and indicators are fully identified by silk-screened nomenclature
    on the cover.
  • UL 294 and UL 1076 recognized components.

Dimensions
5.8" W x 4.825" H x 1.275" D (147.32 mm x 122.55 mm x 32.38 mm)

Weight: 12.4 oz (.35 kg)

Power Supply Requirements
50 mA @ 9-18 VDC
Recommended: Supervised linear power supply with battery back-up, input surge protection, and AC fail and battery low contact outputs.
Separate supervised DC supply with battery back-up recommended for relay activated devices.

Cable Distance
RS-485 – 4000 feet (1220 m) to host, using Belden 3105A,
22AWG twisted pair, shielded 100Ω cable Input Circuits – 500 feet (150 m), two-conductor, shielded,using ALPHA 1292C (22AWG) or Alpha 2421C (18AWG)
Output Circuits – 500 feet (150 m), 2-conductor, using ALPHA
1172C (22AWG) or Alpha 1897C (18AWG)
Minimum wire gauge depends on cable length and current requirements.

Operating Environment
Indoors, or customer-supplied NEMA-4 rated enclosure

Temperature
32° to 122° F (0° to 50° C)

Humidity
5% to 95% relative, non-condensing

Communications Ports
RS-485 - two wire.
Input Circuit Supervision
Configurable for EO resistor values of 1K through 10K. Can
also be configured for use as unsupervised circuits.

Certifications
UL 294 and UL 1076 Recognized Component for the US
CSA 205 for Canada
FCC Class A Verification
EMC for Canada, EU (CE Mark), Australia (C-Tick Mark),
New Zealand, Japan
EN 50130-4 Access Control Systems Immunity for the
EU (CE Mark)