Products

HID® Proximity MiniProx® Hazardous Location 5365

125 kHz mullion mount proximity card reader
HID Proximity MiniProx Hazardous Location 5365
Overview
Specifications
  • Accepts 5 to16 volts, meeting most voltage requirements.
  • Available with Wiegand or Clock-and-data interface.
  • Allows easy upgrade from magstripe to a proximity reader; no rewiring or pulling of new cable required.
  • Offers high reliability, consistent read-range and low power consumption in an easy-to-install package.
  • Mounts directly onto metal with no change in read range performance.
  • Provides multicolor LED, compatibility with all standard access control systems and internal or host control of LED and beeper.
  • Rated Hazardous Locations Class I, Div. 2, Groups A,B,C,D. (US, and Canada)

The Hazardous Location MiniProx provides the same features and dimensions as the MiniProx reader, with an incorporated junction box rated for use in hazardous locations. The junction box is attached to an appropriate surface location utilizing four holes.

Typical maximum* read range:

  • ProxCard® II card - up to 5.5" (14 cm)
  • ISOProx® II card - up to 5" (12.5 cm)
  • ProxKey™ II keyfob - up to 2" (5 cm)
  • ProxCard® Plus card - up to 2" (5 cm)
  • SmartProx™ II card - up to 5" (12.5 cm)

*Depending on local installation conditions.

Dimensions:

  • 6.0" x 1.7" x 1.0"
  • (15.2 x 4.3 x 2.54 cm)

Material
Polycarbonate UL 94

Power supply:

  • Standard MiniProx: 5.1-16 VDC
  • Haz. Loc. MiniProx: 5.1-16 VDC
  • Linear power supplies are recommended.

Current requirements:

  • Average: 40 mA (5 VDC); 50 mA (12 VDC)
  • Peak: 60 mA (5 VDC); 120 mA (12 VDC)

Operating temperature
-22º to 150º F (-30º to 65º C)

Operating humidity
0-95% relative humidity non-condensing

Weight:

  • With terminal strip 3.5 oz. (99 gm)
  • With pigtail 3.8 oz. (108 gm)
  • Haz. Loc. MiniProx: 3.8 oz. (108 gm)

Transmit frequency
125 kHz

Excite frequency
125 kHz

Certifications:

  • Canada/UL 294 Listed: Access Control System Units
  • Canada/UL 1604 Listed (with Haz. Loc. junction box only):
  • Hazardous Locations Class I, Div. 2, Groups A,B,C,D.
  • FCC Certification, United States
  • Canada Certification
  • CE Mark, Europe
  • UK Type Approval
  • Germany Type Approval
  • Australia C-Tick Mark
  • New Zealand EMC

Cable distance:

  • Wiegand interface: 500 feet (150 m)
  • Clock-and-data interface: 50 feet (15 m)
  • Recommended cable is ALPHA 1295 (22 AWG) 5 conductor minimum stranded with overall shield or equivalent. Additional conductors may be required for LED or beeper control.